Compressed air is air kept under a pressure that is greater than atmospheric pressure. It serves many domestic and industrial purposes.

In Europe, 10 percent of all industrial electricity consumption is to produce compressed air—amounting to 80 terawatt hours consumption per year.

In industry, compressed air is so widely used that it is often regarded as the fourth utility, after electricity, natural gas and water. However, compressed air is more expensive than the other three utilities when evaluated on a per unit energy delivered basis.

Compressed air is used for many purposes, including:

The header piping up to the air dryers is exposed to moist, hot air (temperatures can reach well over 150 degrees F). Copper, stainless steel and other piping materials that are less corrosive are recommended. If plain carbon steel piping is installed, then rust particles can pass downstream and interfere with the operation of condensate valves and wye strainers. The riser piping should connect to the top of the header piping and be one pipe size larger than the compressor discharge piping and/or overhead header piping. A drip leg with a drain is needed to prevent water from flowing back to the compressor. Mount valves in the highest horizontal piping (this avoids the hazard of opening a closed valve in vertical piping, and releasing trapped condensate to flow back into air compressors). All of the header main compressed air piping should slope 1/8" to 1/4" per foot down and away from the point of origin. Gravity and airflow will then carry condensate to the low points where a drop leg should be installed to allow for removal at accessible drop legs and drain points. These drops should be installed every 50 to 70 feet in the system and be taken from the bottom of the main line to insure as much removal as possible.

The inlet piping for air dryers should connect to the bottom of the piping headers.

Where multiple air compressors are to connect the riser piping to the top of overhead piping headers. The inlet piping for Air Dryer(s) should connect to the bottom of the piping headers. It is recommended for the inlet pipe to be thermostatically controlled to automatically open and close based on the compressed air room’s temperature.

All of the header main compressed air piping should slope 1/8" per foot down from the air compressor. Gravity and airflow will then carry condensate to the low points where drop leg should be installed to allow for removal at to accessible drop legs and drain points. For larger plant, as the piping elevation lowers, a full size tee with a bottom drip leg preceding an elbow turned up to raise the pipe elevation. These drip legs & up turned elbows are typically 200 to 300 feet apart, i.e. the main piping slopes about 1/100 feet, and the elbow up raises the piping elevation 2 to 3 feet.


...