Heat detector


A heat detector is a fire alarm device designed to respond when the convected thermal energy of a fire increases the temperature of a heat sensitive element. The thermal mass and conductivity of the element regulate the rate flow of heat into the element. All heat detectors have this thermal lag. Heat detectors have two main classifications of operation, "rate-of-rise" and "fixed temperature." The Heat detector is used to help in the reduction of damaged property. It is triggered when temperature increases.

This is the most common type of heat detector. Fixed temperature detectors operate when the heat sensitive eutectic alloy reaches the eutectic point changing state from a solid to a liquid. Thermal lag delays the accumulation of heat at the sensitive element so that a fixed-temperature device will reach its operating temperature sometime after the surrounding air temperature exceeds that temperature. The most common fixed temperature point for electrically connected heat detectors is 136.4°F (58°C). Technological developments have enabled the perfection of detectors that activate at a temperature of 117°F (47°C), increasing the available reaction time and margin of safety.

Rate-of-Rise (ROR) heat detectors operate on a rapid rise in element temperature of 12° to 15°F (6.7° to 8.3°C) increase per minute, irrespective of the starting temperature. This type of heat detector can operate at a lower temperature fire condition than would be possible if the threshold were fixed. It has two heat-sensitive thermocouples or thermistors. One thermocouple monitors heat transferred by convection or radiation. The other responds to ambient temperature. Detector responds when first’s temperature increases relative to the other.

Rate of rise detectors may not respond to low energy release rates of slowly developing fires. To detect slowly developing fires combination detectors add a fixed temperature element that will ultimately respond when the fixed temperature element reaches the design threshold.

Heat detectors commonly have a label on them that says "Not a life safety device". That is because heat detectors are not meant to replace smoke detectors in the bedrooms or in the hallway outside of the bedrooms. A heat detector will nonetheless notify of a fire in a kitchen or utility area (i.e., laundry room, garage, or attic), where smoke detectors should not be installed. This will allow extra time to evacuate the building or to put out the fire if possible.


...