Network protector


A network protector is a type of electric protective device used in electricity distribution systems. The network protector automatically disconnect its associated power transformer from the secondary network when the power starts flowing in reverse direction. Network protectors are used on both spot networks and grid networks. The secondary grid system improves continuity of service for customers, since multiple sources are available to supply the load; a fault with any one supply is automatically isolated by the network protector and does not interrupt service from the other sources. Secondary grids are often used in downtown areas of cities where there are many customers in a small area.

Typically the network protector is set to close when the voltage difference and phase angle are such that the transformer will supply power to the secondary grid, and is set to open when the secondary grid would back-feed through the transformer and supply power to the primary circuit.

Network protectors typically have three settings, "automatic", "open", and "close". The top side is fed from multiple protectors and is always energized unless all units on a spot network are in the open position. Grid units will always be energized on the top side from the many other units tied into the grid. A spot network is 2 or more transformers dedicated to a single customer. The grid feeds multiple customers. A network protector has a circuit breaker set of contacts and a controlling protection relay. The components are enclosed in a protective housing; some network protectors are installed on transformers below grade and must be in water-resistant enclosures. The mechanism contains electrical and mechanical parts to switch open and close the secondary contacts. The controlling relay monitors voltage and current in the transformer, and opens or closes the contact mechanism through electrical signals. The relay uses a power/time curve so that small, short term reverse power flow (such as from elevator hoists) are ignored. Spot units will be 277/480 and the grid units will be 125/216.

The network protector does not protect the (secondary) network cable from overload. The network protector is installed to protect the stability and reliability of the secondary grid by preventing power flow away from the customers and into the primary feeders.


...
Wikipedia

...