Dot convention


The Polarity or Dot Notation for a device with mutual inductance designates the relative instantaneous current directions of such device's winding leads.

The physical criteria of this notation is to preserve a proper magnetic flow circuit direction inside the material. Keeping all current entering a transformer or coupled inductances, in phase, through dotted leads or ports will keep the magnetic flow circulating without canceling each other, and the device will work under their rated efficiency.

Entering current on different dotted ports -one in a dotted port and the other with an un-dotted port- will cause the magnetic flow components to subtract each other, making the device working inefficiently. This criteria holds for devices with several coils, in order to have each of them aggregating in an additive way by entering dotted ports.

Leads of primary and secondary windings are said to be of the same polarity when instantaneous current entering the primary winding lead results in instantaneous current leaving the secondary winding lead as though the two leads were a continuous circuit. In the case of two windings wound around the same core in parallel, for example, the polarity will be the same on the same ends: A sudden (instantaneous) current in the first coil will induce a voltage opposing the sudden increase (Lenz's law) in the first and also in the second coil, because the inductive magnetic field produced by the current in the first coil traverses the two coils in the same manner. The second coil will, therefore, show an induced current opposite in direction to the inducing current in the first coil. Both leads behave like a continuous circuit, one current entering into the first lead and another current leaving the second lead.

A dot marking convention, or alphanumeric marking convention, or both, can be used to denote the same relative instantaneous polarity of two mutually inductive components such as between transformer windings. These markings may be found on transformer cases beside terminals, winding leads, nameplates, schematic and wiring diagrams.

Two methods are commonly used to denote which terminals present the same relative polarity. A dot may be used, or an alphanumeric designation. Alphanumeric designations are typically in the form H1 for primaries, and for secondaries, X1, (and Y1, Z1, if more windings present).

Unlike single-phase transformers, three-phase transformers may incorporate a phase shift due to different winding configurations resulting in a multiple of 30 degree phase shift between H1 and X1 bushing designations.


...